Kryopac Secondary circuit systems

Single fluid systems from -150 up to 280 °C

LAUDA Heating and cooling systems from the line of secondary circuit systems in the KP (Kryopac) model series always consist of the modules, circulating pump, expansion tank electric heater and the special Kryopac system – a heat exchanger which has been developed for evaporating liquid nitrogen. This system enables low temperature reactions to be safely controlled. The heat technology originates from the well-proven modules of the heat transfer systems. The Kryopac units produce a thermostatically controlled liquid flow and are supplied as a compact, fully insulated system with a control cabinet, ready for connection and completely pretested in the factory. Freezing problems in the heat exchangers are a thing of the past. Commercially available heat carriers can be practically cooled down to the solidifi cation point. The LAUDA technology makes it possible to precisely approach this point. A compact design, high safety standard and favorable price are further advantages of the Kryopac system.

Download our HKS brochure:

LAUDA HKS Brochure (9.5 MB)

Technical Data for the LAUDA Kryopac line

Technical Features KP 150 (Ex) KP 250 (Ex) KP 350 (Ex) KP 400 (Ex) KP 600 (Ex)
Heat transfer fluid Thermal oil, special liquids
Working temperature (°C) – 150 … 280 – 150 … 280 – 150 … 280 – 150 … 280 – 150 … 280
Pump flow rate (m³/h) 0.5 … 2 2 … 4 4 … 10 10 … 30 30 … 80
Heater power (kW) 3 … 6 9 … 12 18 … 50 60 … 100 125 … 500
Cooling output at – 100 °C (kW) up to 5 up to 10 up to 15 up to 30 up to 80
Dimensions min. (mm) 500 x 100
x 1500
600 x 1500
x 1500
800 x 1700
x 1500
1000 x 1500
x 1900
1500 x 2200
x 2000
Dimensions max. (mm) 600 x 1500
x 1500
800 x 1700
x 1500
1000 x 1500
x 1900
1300 x 1900
x 2000
2000 x 2500
x 2000