Process
cooling
systems

Cooling systems from -100 up to 150 °C

LAUDA Heating and cooling systems from the line of process cooling systems in the SUK model series always consist of the compressor, pump, expansion tank, evaporator and condenser modules. Depending on the lowest operating temperature, single-stage (down to -35 °C) or two-stage compressors (down to -50 °C) are used and with very low temperatures two cooling circuits are used in cascade (down to -100 °C). The condenser can be cooled by water or air. The output is continuously and precisely controlled by the injection controller. If multiple compressors are present, stage switching saves energy and ensures low-wear partial load operation (automatic compressor system). With an electric heater or a steam heat exchanger the SUK model series can be expanded for temperatures from -100 up to 150 °C. Also precooling using in-house brine or air can be easily realized using the building kit. The application itself dictates whether a cold storage buffer tank is advantageous or not.

Download our HKS brochure:

LAUDA HKS Brochure (9.5 MB)

TECHNICAL DATA FOR LAUDA Process Cooling Systems

Technical Features SUK 150
W/L(Ex)
SUK 250
W/L(Ex)
SUK 350
W/L(Ex)
SUK 400
W/L(Ex)
SUK 600
W/L(Ex)
SUK 1000
W/L(Ex)
Heat transfer fluid Water, water/glycol, thermal oil, special liquids
Working temperature (°C) – 40 … 150 – 50 … 150 – 70 … 150 – 100 … 150 – 100 … 150 – 100 … 150
Pump flow rate (m³/h) 0.5 … 2 2 … 6 2 … 20 4 … 30 5 … 50 10 … 80
Heater power (kW) up to 9 up to 18 up to 50 up to 60 up to 120 up to 240
Single-stage compressor
Cooling output at 20 °C (kW) up to 10 up to 20 up to 50 up to 150 up to 300 up to 400
Cooling output at 0 °C (kW) up to 5 up to 15 up to 35 up to 120 up to 240 up to 300
Cooling output at – 20 °C (kW) up to3 up to 6 up to 18 up to 60 up to 120 up to 180
Cooling output at – 40 °C (kW) up to 1 up to 2 up to 7 up to 45 up to 90 up to 120
Two-stage compressor
Cooling output at – 50 °C (kW) up to 1 up to 4 up to 35 up to 70 up to 90
Two-stage cascade
Cooling output at – 60 °C (kW) up to 3 up to 25 up to 50 up to 70
Cooling output at – 70 °C (kW) up to 2 up to 10 up to 20 up to 35
Cooling output at – 80 °C (kW) up to 0.5 up to 5 up to 10 up to 20
Dimensions min. (mm) 400 x 800
x 1000
500 x 1000
x 1500
800 x 1700
x 1500
1000 x 1500
x 1900
1500 x 2200
x 2000
1500 x 2200
x 2000
Dimensions max. (mm) 500 x 1000
x 1500
600 x 1500
x 1500
1000 x 1500
x 1900
1300 x 1900
x 2000
200 x 2500
x 2000
200 x 2500
x 2000
Technical Features KH 150
W/L(Ex)
KH 250
W/L(Ex)
KH 350
W/L(Ex)
KH 400
W/L(Ex)
KH 600
W/L(Ex)
KH 1000
W/L(Ex)
Heat transfer fluid Thermal oil, special liquids
Working temperature (°C) – 40 … 250 – 50 … 250 – 70 … 250 – 100 … 250 – 100 … 250 – 100 … 400
Pump flow rate (m³/h) 0.5 … 2 2 … 6 2 … 20 4 … 30 5 … 50 10 … 80
Heater power (kW) up to 9 up to 18 up to 50 up to 60 up to 120 up to 240
Single-stage compressor
Cooling output at 20 °C (kW) up to 10 up to 20 up to 50 up to 150 up to 300 up to 400
Cooling output at 0 °C (kW) up to 5 up to 15 up to 35 up to 120 up to 240 up to 300
Cooling output at – 20 °C (kW) up to3 up to 6 up to 18 up to 60 up to 120 up to 180
Cooling output at – 40 °C (kW) up to 1 up to 2 up to 7 up to 45 up to 90 up to 120
Two-stage compressor
Cooling output at – 50 °C (kW) up to 1 up to 4 up to 35 up to 70 up to 90
Two-stage cascade
Cooling output at – 60 °C (kW) up to 3 up to 35 up to 50 up to 70
Cooling output at – 70 °C (kW) up to 2 up to 10 up to 20 up to 35
Cooling output at – 80 °C (kW) up to 0.5 up to 5 up to 10 up to 20
Dimensions min. (mm) 500 x 1000
x 1500
600 x 1000
x 1500
800 x 1700
x 1500
1000 x 1500
x 1900
1500 x 2200
x 2000
1500 x 2200
x 2000
Dimensions max. (mm) 600 x 1500
x 1500
800 x 1700
x 1500
1000 x 1500
x 1900
1300 x 1900
x 2000
200 x 2500
x 2000
200 x 2500
x 2000

Your advantages at a glance

R

Digital temperature controller
for controlling the consumer / product temperature and the outflow temperature.

R

Automatic shut-off valve on cooling water inlet
to avoid contamination of the heat exchanger.

R

Continuously controlled stainless steel electric heater as a flange version
thus, the heating power is adapted to the actual energy requirements

R

Highly dynamic, energy-efficient cooling system
thanks to modern cooling modules for the best possible configuration of compressor and performance quantity.

R

Hermetic version without seals
so that oils and water are not mixed.

R

FAT (Factory Acceptance Test) in presence of customer
to check that the systems are designed for customer requirements and to provide an initial instruction and trial run already before shipment.